Control cable for a PLC or DCS cabinet underground is often bought from a catalogue by core count and cross-section. That is enough to make the cable fit, but not enough to make the circuit reliable. The specification should also describe the signal, the interference environment, the route and the termination method.
Digital I/O, analogue 4–20 mA loops and drive feedback have different noise profiles. A 24 V digital signal can tolerate more interference than a low-level analogue measurement, but it can still misread if a nearby contactor or a shearer drive generates a fast transient. For analogue loops, describe the signal level, the source impedance and whether the circuit is single-ended or differential.
If the circuit enters a hazardous area, or passes through a goaf or a sealed zone, say so at the start. Intrinsically safe circuits may require a blue sheath, a foil screen and a defined earth path. Those requirements change the construction and the documentation.
Screening is not automatic. Use a screen when the circuit runs near variable-speed drives, conveyor starters, switching power supplies or high-current conductors. Copper braid is robust and gives good high-frequency performance. Aluminium/polyester foil with a drain wire is lighter and cost-effective for static screening. For the noisiest faces, an individual screen plus an overall screen may be appropriate — see our shielded mining control cable range.
A cable in a panel duct, a cable in a roadway tray and a cable trailing behind a shearer are three different products. Fixed roadway routes usually justify steel wire or steel tape armour. Coal face and mobile equipment point to a flexible rubber construction. Wet, dusty or oil-contaminated conditions may require a chloroprene sheath or an LSZH compound.
Ask for the construction drawing and the order-specific datasheet. Check the conductor class, because Class 1, Class 2 and Class 5 conductors behave differently in terminals and in moving routes. Check the screen coverage and the drain wire. Check the sheath compound and the temperature rating. Finally, confirm the length and drum marking, especially where cable is pulled in stages down a shaft.
If you send those details to our team, we will review the construction and confirm what is standard, what is optional and what needs to be custom-made. Browse the mining control cable range first, or send the route drawing directly.
Mining shielded control cable · Mining armoured power cable · Mining intrinsically safe communication cable